WennSoft has predefined sensor calculations to choose from when creating your calculated sensors.
|
Name |
Formula |
|---|---|
|
Cooling Air Temperature Deviation |
Cooling Air Temperature Setpoint - Cooling Air Temperature |
|
Chilled Water Approach |
(Evaporator Leaving Water Temperature) – (Evaporator Saturated Refrigerant Temperature) |
|
Condenser Water Approach |
(Condenser Saturated Refrigerant Temperature) – (Condenser Leaving Water Temperature) |
|
Chilled Water Delta T |
(Evaporator Entering Water Temp) – (Evaporator Leaving Water Temp) |
|
Condenser Water Delta T |
(Condenser Leaving Water Temp) – (Condenser Entering Water Temp) |
|
Differential Steam Pressure Deviation |
(abs(Differential Steam Pressure Setpoint - Differential Steam Pressure) / max(0.1, Differential Steam Pressure Setpoint)) * 100 |
|
Differential Water Pressure Deviation |
(abs(Differential Water Pressure Setpoint - Differential Steam Pressure) / max(0.1, Differential Water Pressure Setpoint)) * 100 |
|
Heating Air Temperature Deviation |
Heating Air Temperature Setpoint - Heating Air Temperature |
|
Outside Air Dewpoint |
Celcius to Celsius Formula
Fahrenheit to Fahrenheit Formula
Fahrenheit to Celcius Formula
T: Outside Air temperature
T and RH are existing sensors. |
|
Outside Air Wet Bulb |
Celcius to Celsius Formula
Fahrenheit to Fahrenheit Formula
Fahrenheit to Celcius Formula
T: Outside Air temperature
T and RH are existing sensors. |
|
Power |
Current * Voltage |
|
Power (kVa) *coming soon |
Power + Power + Power + Power |
|
Primary Differential Water Pressure Deviation |
(abs(Primary Differential Water Pressure Setpoint - Primary Differential Water Pressure) / max(0.1, Primary Differential Water Pressure Setpoint)) * 100 |
|
Primary Supply Water Temperature |
Primary Supply Water Temperature Setpoint - Primary Supply Water Temperature |
|
Secondary Differential Water Pressure Deviation |
(abs(Secondary Differential Water Pressure Setpoint - Secondary Differential Water Pressure) / max(0.1, Secondary Differential Water Pressure Setpoint)) * 100 |
|
Secondary Supply Water Temperature Deviation |
Secondary Supply Water Temperature Setpoint - Secondary Supply Water Temperature |
|
Space Air CO Deviation |
Space Air CO Setpoint - Space Air CO |
|
Space Air CO2 Deviation |
Space Air CO2 Setpoint - Space Air CO2 |
|
Space Air Dewpoint |
Space Air Temperature(C) - ((100 - Space Air Relative Humidity) / 5) |
|
Space Air Methane Deviation |
Space Air Methane Setpoint - Space Air Methane |
|
Space Air PM2.5 Deviation |
Space Air PM2.5 Setpoint - Space Air PM2.5 |
|
Space Air Relative Humidity Deviation |
Space Air Relative Humidity Setpoint - Space Air Relative Humidity |
|
Space Air Temperature Deviation |
Space Air Temperature Setpoint - Space Air Temperature |
|
Space Air TVOC Deviation |
Space Air TVOC Setpoint - Space Air TVOC |
|
Supply Air Flow Deviation |
(abs(Supply Air Flow Setpoint - Supply Air Flow) / max(0.1, Supply Air Flow Setpoint)) * 100 |
|
Supply Air Pressure Deviation |
(abs(Supply Air Pressure Setpoint - Supply Air Pressure) / max(0.1, Supply Air Pressure Setpoint)) * 100 |
|
Supply Air Temperature Deviation |
Supply Air Temperature - Supply Air Temperature Setpoint |
|
Supply Water Flow Deviation |
(abs(Supply Water Flow Setpoint - Supply Water Flow) / max(0.1, Supply Water Flow Setpoint)) * 100 |
|
Supply Water Temperature Deviation |
Supply Water Temperature Setpoint - Supply Water Temperature |
|
Total Runtime |
Sum of Time for time given for a True condition. |